27.pdf

(8305 KB) Pobierz
Antenna and
Transmission-Line
Measurements
Chapter
27
The principal quantities measured on transmission lines
are line current or voltage, and standing-wave ratio (SWR).
You make measurements of current or voltage to determine
the power input to the line. SWR measurements are useful
in connection with the design of coupling circuits and the
adjustment of the match between the antenna and
transmission line, as well as in the adjustment of these
matching circuits.
For most practical purposes a relative measurement is
sufficient. An uncalibrated indicator that shows when the
largest possible amount of power is being put into the line is
just as useful, in most cases, as an instrument that measures
the power accurately. It is seldom necessary to know the
actual number of watts going into the line unless the overall
efficiency of the system is being investigated. An instrument
that shows when the SWR is close to 1:1 is all you need for
most impedance-matching adjustments. Accurate
measurement of SWR is necessary only in studies of antenna
characteristics such as bandwidth, or for the design of some
types of matching systems, such as a stub match.
Quantitative measurements of reasonable accuracy
demand good design and careful construction in the
measuring instruments. They also require intelligent use of
the equipment, including a knowledge not only of its
limitations but also of stray effects that often lead to false
results. Until you know the complete conditions of the
measurements, a certain amount of skepticism regarding
numerical data resulting from amateur measurements with
simple equipment is justified. On the other hand, purely
qualitative or relative measurements are easy to make and
are reliable for the purposes mentioned above.
indicator. In many cases, particularly with a screen-grid tube
in the final stage, minimum loaded plate current does not
occur simultaneously with maximum power output.
RF VOLTMETER
You can put together a germanium diode in conjunction
with a low-range milliammeter and a few resistors to form
an RF voltmeter suitable for connecting across the two
conductors of a coaxial line, as shown in Fig 1 . It consists of
a voltage divider, R1-R2, having a total resistance about 100
times the Z 0 of the line (so the power consumed will be
negligible) with a diode rectifier and milliammeter connected
across part of the divider to read relative RF voltage. The
purpose of R3 is to make the meter readings directly
proportional to the applied voltage, as nearly as possible, by
swamping the resistance of D1, since the diode resistance
will vary with the amplitude of the current through the diode.
LINE CURRENT AND VOLTAGE
A current or voltage indicator that can be used with
coaxial line is a useful piece of equipment. It need not be
elaborate or expensive. Its principal function is to show when
the maximum power is being taken from the transmitter; for
any given set of line conditions (length, SWR, etc). This
will occur when you adjust the transmitter coupling for
maximum current or voltage into the transmission line.
Although the final-amplifier plate or collector current meter
is frequently used for this purpose, it is not always a reliable
Fig 1
RF voltmeter for coaxial line.
C1, C2
0.005- or 0.01-
µ
F ceramic.
D1
Germanium diode, 1N34A.
J1, J2
Coaxial fittings, chassis-mounting type.
M1
0-1 milliammeter (more sensitive meter may be
used if desired; see text).
R1
6.8 k
Ω
, composition, 1 W for each 100 W of RF
power.
R2
680
Ω
, 1 / 2 or 1 W composition.
R3
10 k
, 1 / 2 W (see text).
Ω
Antenna and Transmission-Line Measurements
27-1
1361083000.050.png 1361083000.061.png 1361083000.072.png 1361083000.083.png 1361083000.001.png
You may construct the voltmeter in a small metal box,
indicated by the dashed line in the drawing, and fitted with
coax receptacles. R1 and R2 should be carbon-composition
resistors. The power rating for R1 should be 1 W for each
100 W of carrier power in the matched line; separate 1- or
2-W resistors should be used to make up the total power rating
required, to the total resistance as given. Any type of resistor
can be used for R3; the total resistance should be such that
about 10 V dc will be developed across it at full scale. For
example, a 0-1 milliammeter would require 10 k
Ω
, a 0-500
microammeter would take 20 k
, and so on. For comparative
measurements only, R3 may be a variable resistor so the
sensitivity can be adjusted for various power levels.
In constructing such a voltmeter, you should exercise
care to prevent inductive coupling between R1 and the loop
formed by R2, D1 and C1, and between the same loop and
the line conductors in the assembly. With the lower end of
R1 disconnected from R2 and grounded to the enclosure,
but without changing its position with respect to the loop,
there should be no meter indication when full power is going
through the line.
If more than one resistor is used for R1, the units should
be arranged end-to-end with very short leads. R1 and R2
should be kept 1 / 2 inch or more from metal surfaces parallel
to the body of the resistor. If you observe these precautions
the voltmeter will give consistent readings at frequencies
up to 30 MHz. Stray capacitance and stray coupling limit
the accuracy at higher frequencies but do not affect the utility
of the instrument for comparative measurements.
Ω
Fig 2
A convenient method of mounting an RF
ammeter for use in a coaxial line. This is a metal-case
instrument mounted on a thin bakelite panel. The
cutout in the metal clears the edge of the meter by
about 1/8 inch.
precaution being that the capacitance to ground, chassis, and
nearby conductors should be low. A bakelite-case instrument
can be mounted on a metal panel without introducing enough
shunt capacitance to ground to cause serious error up to
30 MHz. When installing a metal-case instrument on a metal
panel, you should mount it on a separate sheet of insulating
material so that there is 1 / 8 inch or more separation between
the edge of the case and the metal.
A 2-inch instrument can be mounted in a 2
Calibration
You may calibrate the meter for RF voltage by
comparison with a standard such as an RF ammeter. This
requires that the line be well matched so the impedance at
the point of measurement is equal to the actual Z 0 of the
line. Since in that case P = I 2 Z 0 , the power can be calculated
from the current. Then E Z
4-
inch metal box, as shown in Fig 2 . This is a convenient
arrangement for use with coaxial line. Installed this way, a
good quality RF ammeter will measure current with an
accuracy that is entirely adequate for calculating power in
the line. As discussed above in connection with calibrating
RF voltmeters, the line must be closely matched by its load
so the actual impedance is resistive and equal to Z 0 . The
scales of such instruments are cramped at the low end,
however, which limits the range of power that can be
measured by a single meter. The useful current range is about
3 to 1, corresponding to a power range of about 9 to 1.
×
4
×
= 0 . By making current and
voltage measurements at a number of different power levels,
you can obtain enough points to draw a calibration curve
for your particular setup.
RF AMMETERS
Although they are not as widely available as they used
to be, if you can find one on the surplus market or at a
hamfest, an RF ammeter is a good way to gauge output
power. You can mount an RF ammeter in any convenient
location at the input end of the transmission line, the principal
SWR Measurements
On parallel-conductor lines it is possible to measure
the standing-wave ratio by moving a current (or voltage)
indicator along the line, noting the maximum and
minimum values of current (or voltage) and then
computing the SWR from these measured values. This
cannot be done with coaxial line since it is not possible
to make measurements of this type inside the cable. The
technique is, in fact, seldom used with open lines because
it is not only inconvenient but sometimes impossible to
reach all parts of the line conductors. Also, the method is
27-2
Chapter 27
1361083000.002.png 1361083000.003.png
subject to considerable error from antenna currents flowing
on the line.
Present-day SWR measurements made by amateurs
practically always use some form of directional coupler or
RF-bridge circuit. The indicator circuits themselves are
fundamentally simple, but they require considerable care in
construction to ensure accurate measurements. The
requirements for indicators used only for the adjustment of
impedance-matching circuits, rather than actual SWR
measurement, are not so stringent, and you can easily make
an instrument for this purpose.
BRIDGE CIRCUITS
Two commonly used bridge circuits are shown in Fig 3 .
The bridges consist essentially of two voltage dividers in
parallel, with a voltmeter connected between the junctions
of each pair of arms , as the individual elements are called.
When the equations shown to the right of each circuit are
satisfied there is no potential difference between the two
junctions, and the voltmeter indicates zero voltage. The
bridge is then said to be in balance .
Taking Fig 3A as an illustration, if R1 = R2, half the
applied voltage, E, will appear across each resistor. Then if
R S = R X , 1 / 2 E will appear across each of these resistors and
the voltmeter reading will be zero. Remember that a matched
transmission line has essentially a purely resistive input
impedance. Suppose that the input terminals of such a line
are substituted for R X . Then if R S is a resistor equal to the
Z 0 of the line, the bridge will be balanced.
If the line is not perfectly matched, its input impedance
will not equal Z 0 and hence will not equal R S , since you
chose the latter to be equal to Z 0 . There will then be a
difference in potential between points X and Y, and the
voltmeter will show a reading. Such a bridge therefore can
be used to show the presence of standing waves on the line,
because the line input impedance will be equal to Z 0 only
when there are no standing waves.
Considering the nature of the incident and reflected
components of voltage that make up the actual voltage at
the input terminals of the line, as discussed in Chapter
24 , it should be clear that when R S = Z 0 , the bridge is
always in balance for the incident component. Thus the
voltmeter does not respond to the incident component at
any time but reads only the reflected component
(assuming that R2 is very small compared with the
voltmeter impedance). The incident component can be
measured across either R1 or R2, if they are equal
resistances. The standing-wave ratio is then
Fig 3
Bridge circuits suitable for SWR measurement.
At A, Wheatstone type using resistance arms. At B,
capacitance-resistance bridge (“Micromatch”).
Conditions for balance are independent of frequency
in both types.
1
1–
+
k
k
SWR
=
(Eq 2)
where k = E2/E1.
The operation of the circuit in Fig 3B is essentially the
same, although this circuit has arms containing reactance as
well as resistance.
It is not necessary that R1 = R2 in Fig 3A; the bridge
can be balanced, in theory, with any ratio of these two
resistances provided R S is changed accordingly. In practice,
however, the accuracy is highest when the two are equal;
this circuit is most commonly used.
A number of types of bridge circuits appear in Fig 4 ,
many of which have been used in amateur products or
amateur construction projects. All except that at G can have
the generator and load at a common potential. At G, the
generator and detector are at a common potential. You may
interchange the positions of the detector and transmitter (or
generator) in the bridge, and this may be advantageous in
some applications.
The bridges shown at D, E, F and H may have one
terminal of the generator, detector and load common. Bridges
at A, B, E, F, G and H have constant sensitivity over a wide
frequency range. Bridges at B, C, D and H may be designed
to show no discontinuity (impedance lump) with a matched
line, as shown in the drawing. Discontinuities with A, E and
F may be small.
Bridges are usually most sensitive when the detector
bridges the midpoint of the generator voltage, as in G or H, or
in B when each resistor equals the load impedance. Sensitivity
also increases when the currents in each leg are equal.
EE
EE
+12
12
SWR
=
(Eq 1)
–
where E1 is the incident voltage and E2 is the reflected
voltage. It is often simpler to normalize the voltages by
expressing E2 as a fraction of E1, in which case the formula
becomes
Antenna and Transmission-Line Measurements
27-3
1361083000.004.png 1361083000.005.png 1361083000.006.png 1361083000.007.png 1361083000.008.png 1361083000.009.png 1361083000.010.png 1361083000.011.png
 
Fig 4 Various types of SWR indicator circuits and commonly known names of bridge circuits or devices in that
they have been used. Detectors (D) are usually semiconductor diodes with meters, isolated with RF chokes and
capacitors. However, the detector may be a radio receiver. In each circuit, Z represents the load being measured.
(This information provided by David Geiser, WA2ANU)
27-4
Chapter 27
1361083000.012.png 1361083000.013.png 1361083000.014.png 1361083000.015.png 1361083000.016.png 1361083000.017.png 1361083000.018.png 1361083000.019.png 1361083000.020.png 1361083000.021.png 1361083000.022.png 1361083000.023.png 1361083000.024.png 1361083000.025.png 1361083000.026.png 1361083000.027.png 1361083000.028.png 1361083000.029.png 1361083000.030.png 1361083000.031.png 1361083000.032.png 1361083000.033.png 1361083000.034.png 1361083000.035.png 1361083000.036.png 1361083000.037.png 1361083000.038.png 1361083000.039.png 1361083000.040.png 1361083000.041.png 1361083000.042.png 1361083000.043.png 1361083000.044.png 1361083000.045.png 1361083000.046.png 1361083000.047.png 1361083000.048.png 1361083000.049.png 1361083000.051.png 1361083000.052.png 1361083000.053.png 1361083000.054.png 1361083000.055.png 1361083000.056.png 1361083000.057.png 1361083000.058.png 1361083000.059.png 1361083000.060.png 1361083000.062.png 1361083000.063.png 1361083000.064.png 1361083000.065.png 1361083000.066.png 1361083000.067.png 1361083000.068.png 1361083000.069.png 1361083000.070.png 1361083000.071.png 1361083000.073.png 1361083000.074.png 1361083000.075.png 1361083000.076.png 1361083000.077.png 1361083000.078.png 1361083000.079.png 1361083000.080.png 1361083000.081.png 1361083000.082.png 1361083000.084.png 1361083000.085.png 1361083000.086.png 1361083000.087.png 1361083000.088.png
 
Resistance Bridge
The basic bridge configuration shown in Fig 3B may
be home constructed and is reasonably accurate for SWR
measurement. A practical circuit for such a bridge is given
in Fig 5 and a representative layout is shown in Fig 6 .
Properly built, a bridge of this design can be used for
measurement of SWRs up to about 15:1 with good accuracy.
You should observe these important construction
points:
1) Keep leads in the RF circuit short, to reduce stray
inductance.
2) Mount resistors two or three times their body diameter
away from metal parts, to reduce stray capacitance.
3) Place the RF components so there is as little inductive and
capacitive coupling as possible between the bridge arms.
proportional to the RF voltage) and no voltage calibration
curve is needed. D1 is the rectifier for the reflected voltage
and D2 is for the incident voltage. Because of manufacturing
variations in resistors and diodes, the readings may differ
slightly with two multipliers of the same nominal resistance
value, so a correction resistor, R3, is included in the circuit.
You should select its value so that the meter reading is the
same with S1 in either position, when RF is applied to the
bridge with the line connection open. In the instrument
shown, a value of 1000
was required in series with the
multiplier for reflected voltage; in other cases different values
probably would be needed and R3 might have to be put in
series with the multiplier for the incident voltage. You can
determine this by experiment.
The value used for R1 and R2 is not critical, but you
should match the two resistors within 1% or 2% if possible.
Keep the resistance of R S as close as possible to the actual
Z 0 of the line you use (generally 50 or 75
Ω
In the instrument shown in Fig 6 , the input and line
connectors, J1 and J2, are mounted fairly close together so
the standard resistor, R S , can be supported with short leads
directly between the center terminals of the connectors. R2
is mounted at right angles to R S , and a shield partition is
used between these two components and the others.
The two 47-k
). Select the
resistor by actual measurement with an accurate resistance
bridge, if you have one available.
R4 is for adjusting the incident-voltage reading to full
scale in the measurement procedure described below. Its use
is not essential, but it offers a convenient alternative to exact
adjustment of the RF input voltage.
Ω
resistors, R5 and R6 in Fig 5, are
voltmeter multipliers for the 0-100 microammeter used as
an indicator. This is sufficient resistance to make the
voltmeter linear (that is, the meter reading is directly
Ω
Testing
Measure R1, R2 and R S with a reliable digital ohmmeter
or resistance bridge after completing the wiring. This will
ensure that their values have not changed from the heat of
soldering. Disconnect one side of the microammeter and leave
the input and output terminals of the unit open during such
measurements to avoid stray shunt paths through the rectifiers.
Check the two voltmeter circuits as described above,
applying enough RF (about 10 V) to the input terminals to
give a full-scale reading with the line terminals open. If
necessary, try different values for R3 until the reading is the
same with S1 in either position.
With J2 open, adjust the RF input voltage and R4 for
full-scale reading with S1 in the incident-voltage position.
Then switch S1 to the reflected-voltage position. The reading
should remain at full scale. Next, short-circuit J2 by touching
a screwdriver between the center terminal and the frame of
the connector to make a low-inductance short. Switch S1 to
the incident-voltage position and readjust R4 for full scale,
if necessary. Then throw S1 to the reflected-voltage position,
keeping J2 shorted, and the reading should be full scale as
before. If the readings differ, R1 and R2 are not the same
value, or there is stray coupling between the arms of the
bridge. You must read the reflected voltage at full scale with
J2 either open or shorted, when the incident voltage is set to
full scale in each case, to make accurate SWR measurements.
The circuit should pass these tests at all frequencies at
which it is to be used. It is sufficient to test at the lowest and
highest frequencies, usually 1.8 or 3.5 and 28 or 50 MHz.
Fig 5 Resistance bridge for SWR measurement.
Capacitors are disc ceramic. Resistors are 1 / 2 -watt
composition except as noted below.
D1, D2
Germanium diode, high back resistance type
(1N34A, 1N270, etc).
J1, J2
Coaxial connectors, chassis-mounting type.
M1
0-100 dc microammeter.
R1, R2
, 1 / 2 -W composition (see text).
R3 See text.
R4
47
Ω
50-k
Ω
volume control.
R s
Resistance equal to line Z 0 ( 1 / 2 or 1 W
composition).
S1
SPDT toggle.
Antenna and Transmission-Line Measurements
27-5
1361083000.089.png 1361083000.090.png 1361083000.091.png
Zgłoś jeśli naruszono regulamin